1
|
实验室内的电源容量过小,不能满足仪器的供电要求,尤其要重点核查理化实验室和洗消间,必须保证这些(每间)实验室有三相电源,最小容量不能低于10kW Low volume of power will not satisfy the power supply of equipments, especially for physical and chemistry lab and wash-infection room, it should be ensured that labs have three-phase power and its minimum volume should not below 10KW.
|
|
|
2
|
接地端子箱的设置,要求每间实验室,尤其是理化实验室必须设置接地端子箱,且接地电阻不得大于1欧姆
Every lab, especially physical chemistry lab should have grounding terminal board and grounding resistance should no more than 1Ω.
|
必须满足要求,设置专用的接地干线和端子箱
It should install grounding main burbar and terminal board.
|
|
3
|
实验室灯具,不得采用链吊式安装,应采用吸顶式
The lightings in lab should not use chain to install and should connect ceiling directly.
|
建议改变灯具的排列方式,数量和安装方式,采用吸顶安装
Change the arrange style, amount and install style and adopt directly connection to ceiling.
|
|
4
|
所有二级生物安全实验室的入口处应安装显示工作状态的文字或灯光信号
The entrance of all the BSL2 should have signs and lighting signs which could show the working condition
|
|
|
5
|
生物安全实验室内应设紧急发光疏散标志
BSL should have emergency escape sign.
|
|
|
6
|
如有集中的气瓶间,则该房间的电具要求采用防爆型. If there is integrated gas container room, the room should adopt flameproof device.
|
|
|
7
|
在生物安全实验室区域设置火灾自动报警装置. BSL should have fire auto-alarm.
|
建议采用区域报警设备,对生物安全实验室进行火灾预警
Local alarm device is preferred in order to give pre-alarm of fire.
|
|
8
|
进入生物实验室的管路没有做密闭,应采取措施,完成此步骤
The pipe which putted into bio lab should be pressurized.
|
|
|
9
|
|
插座没有配置防水罩,建议补加
Socket should be equipped with water-proof cover.
|
|
10
|
|
如存在血清存储、必须冷藏的试剂或是疫苗库,建议提供备用电源.
If there are serum storage, vaccine storage, reagent which should be refrigeration and vaccine storage, back-up power should be provide.
|
|
11
|
|
如有负压二级生物安全实验室提供一条备用电源. BSL2 should have one back-up power.
|
|
12
|
|
生物安全实验室内的电源设置漏电检测报警装置 The power supply of BSL should have leakage alarm device.
|