Dwyer球阀WE07-DDA01-T_WE07-ITD03-T-A_WE07-DTD01-T-A
Electric “TD” and “MD” Series
Power Requirements: 110 VAC,220 VAC, 24 VAC or 24 VDC (MD
models not available in 24 VDC).
Power Consumption: See instruction manual.
Cycle Time (per 90°): TD01: 4 s; MD01: 10 s; TD02 and MD02: 20 s; TD03 and MD03: 30 s.
Duty Rating: 85%.
Enclosure Rating: NEMA 4X (IP67).
Housing Material: Powder coated aluminum.
Temperature Limits: -22 to 140°F (-30 to 60°C).
Electrical Connection: 1/2? female NPT.
Modulating Input: 4 to 20 mA.
Standard Features: Manual override, position indicator, and TD models come with two limit switches.
Electric “TI” and “MI” Series
Power Requirements: 110 VAC,220 VAC, 24 VAC or 24 VDC.
Power Consumption: See instruction manual.
Cycle Time (per 90°): See instruction manual.
Duty Rating: See instruction manual.
Enclosure Rating: NEMA 7, designed to meet hazardous locations: Class I,
Group C & D; Class II, Group E, F & G; Division I & II.
Housing Material: Powder coated aluminum.
Temperature Limits: -40 to 140°F (-40 to 60°C).
Electrical Connection: 1/2? female NPT.
Modulating Input: 4 to 20 mA.
Standard Features: Position indicator and two limit switches.