| 测量原理 | 雷达物位 |
| 特点/应用 | For basic level measurement in liquids, pastes and slurries; non affected by changing media, temperature changes, gas blankets or vapor; Encapsulated PVDF or PP clad horn antenna
|
| 特性 | SIL 2 according to IEC 61508, Safety and reliability with Multi-Echo Tracking, HistoROM
|
| 电源/通信 | 2-wire (HART / PROFIBUS PA/ FOUNDATION Fieldbus) 4-wire (HART)
|
| 频率 | K-band (~26 GHz)
|
| 测量精度 | +/- 2 mm (0.08 in)
|
| 环境温度 | -40...+80 °C (-40...+176 °F)
|
| 过程温度 | -40...+130 °C (-40...+266 °F)
|
| 过程绝压/最大过压界限 | Vacuum...3 bar (Vacuum...43.5 psi)
|
| 接触介质部件 | PVDF, PTFE, Viton, PP, PBT
|
| 过程连接 | Thread: G1 1/2, MNPT1 1/2 Flange: UNI DN80...DN150 (3"...6")
|
| 最大测量距离 | Standard: 30 m (98 ft) With enhanced dynamics: 40 m (131 ft)
|
 | 
|
| 输出 | 4...20 mA HART PROFIBUS PA FOUNDATION Fieldbus
|
| 证书和认证 | ATEX, FM, CSA, CSA C/US, IEC Ex, TIIS, INMETRO, NEPSI, KC
|
| Safety approvals | Overfill prevention WHG SIL
|
| 可选项 | Display Customized parameterization PWIS free
|
| 应用局限 | Maximum measuring range is dependent on the tank form and/or application:
Ammoniacal gas phase: FMR54 in stilling well Strong buildup formation: FMR54 with air purge Low DK: FMR51 Only PTFE resistant: FMR52 Custody transfer measurement: FMR5xx
|