测量原理 | 绝压仪表 |
特点 | Smart and reliable pressure transmitter, with piezoresistive measuring cell and metal welded process isolating diaphragm and diaphragm seal.
|
电源/通信 | 4...20mA HART 11,5...45V DC (Non Ex): Ex ia: 11,5...30V DC PROFIBUS PA: 9...32 V DC (Non Ex) FOUNDATION Fieldbus: 9...32 V DC (Non Ex)
|
测量精度 | Standard 0,15% Platinum 0,075%
|
长期稳定性 | < 0,1% of URL/year 0,2% of URL/ 5 years 0,25% of URL/ 10 years
|
过程温度 | -70°C…400°C (-94°F…752°F)
|
环境温度 | -40°C...85°C (-40°F...185°F)
|
量程 | 400mbar...400bar (15psi...6000psi) relative/ absolute
|
Smallest calibratable span | 20 mbar (2.9 psi) rel./ abs.
|
Vacuum resistance | 50 mbar (7.25psi) abs.
|
开关比 | 20:1
|
最大过压极限 | 600bar (9000psi)
|
过程连接 | Thread: G1/2...G2, MNPT1/2...MNPT2 Flange: DN25...DN100, ASME 1"...4", JIS 10k Diaphragm seal
|
卫生型 | Tri-Clamp DIN11851 DIN11864-1 NEUMO Varivent SMS DRD Universal adapter
|
Material process membrane | 316L, AlloyC, Tantal, PTFE, Rhodium>Gold
|
Material gasket | None, diaphragm welded
|
Fill fluid | Silicone oil, Inert oil, Vegetable oil, High temperature oil, Low temperature oil,
|
Material housing | Die-cast aluminum, AISI 316L
|
输出 | 4...20 mA 4...20 mA HART PROFIBUS PA FOUNDATION Fieldbus
|
证书和认证 | ATEX, FM, CSA, CSA C/US, IEC Ex, TIIS, INMETRO, NEPSI
|
Safety approvals | SIL
|
Design approvals | EN10204-3.1 NACE MR0103
|
Hygienic approvals | CoC ASME-BPE 3A, EHEDG
|
Marine approvals | GL/ ABS/ LR/ BV/ DNV
|
特性 | TempC Membrane |