TG-A
1.1 Protection Class: IP68
1.2:Specification:
Power Supply: DC25V±10%、<3W
Input Range: 0~30 mV
Output Signal: 0~10V,0~5V / 4~20mA ,0~20 mA(adjustable±20%)
1.3:Max. Overload Current Protection:
Power Voltage > AC,DC30V
Output Signal > AC,DC 30V
1.4:Commissioning:
ZERO Zero setting(Self-weight shall not exceed 30% of full capacity,
adjustZEROvariable resistor to a output of 0V or 4mA)
SPAN Capacity setting(Add standard load of full capacity to load-cell,
adjustSPAN variable resistor to a output of 10V or 20mA)
Remark:suggest to repeat the adjustment 3 times;added load shall be 20% over the full capacity
1.5:Parallel Deviation Rectification:
1/ Calibrate three times, to make sure the data is repeatable.
2/ If no full capacity load is available, since the load cell and amplifier have their own linearity, calibrate with part of capacity weight would be acceptable, but remember the lower rate of weight/capacity